Cwfl-6000 Manual -

Check for any shipping damage upon arrival.

CWFL-6000 units manufactured after 2020 include a USB port. Insert a FAT32-formatted USB drive, press and hold the UP arrow for 10 seconds. The manual says the file will be named CWFL_LOG.txt . cwfl-6000 manual

| Code | Error Meaning | Likely Cause | Manual-Recommended Solution | | :--- | :--- | :--- | :--- | | | High-temp over limit ( >40°C) | Dirty condenser, fan failure, ambient too high | Clean condenser fins with compressed air. Check fans. | | E02 | Low-temp over limit ( >35°C) | Optics circuit overload or refrigerant leak | Check QBH for overheating. Contact technician. | | E03 | High-temp under limit ( <5°C) | Ambient too cold or heater failure (if equipped) | Disable winter mode if ambient >25°C. | | E04 | Low flow alarm | Clogged filter, air in system, pump failure | Clean/replace water filter (see Ch.4). Bleed air vents. | | E05 | Phase sequence error (3-phase) | Incorrect L1/L2/L3 wiring | Swap any two input phase wires. | | E06 | Refrigerant high pressure | Blocked condenser or overcharged system | Clean condenser. If persists, call S&A service. | Check for any shipping damage upon arrival

Decrease temperature value or scroll down through parameters. The manual says the file will be named CWFL_LOG

Connect the "Output" to the fiber laser source water inlet, and the "Input" to the laser source water outlet. Filling the Water Tank Open the water fill cap on top of the chiller.

Use a dedicated circuit breaker matching the current specifications found on the chiller’s nameplate.